Information about Differential Motor Regulator 2.5-4A
Miniature Circuit Breaker 2.5-4A Screw Connection TeSys GV2. Short name of the device GV2P. Device application: Motor. Number of poles: 3P. Network type: AC. Utilisation category: AC-3 according to IEC 60947-4-1 Category A according to IEC 60947-2. Rated operational frequency: 50/60 Hz according to IEC 60947-4-1. Breaking capacity: 100 kA Icu at 500 V AC 50/60 Hz according to IEC 60947-2 100 kA Icu at 230/240 V AC 50/60 Hz according to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz according to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz according to IEC 60947-2 8 kA Icu at 690 V AC 50/60 Hz according to IEC 60947-2. [Ics] Rated service short-circuit breaking capacity 100% at 230/240 V AC 50/60 Hz according to IEC 60947-2 100% at 440 V AC 50/60 Hz according to IEC 60947-2 100% at 500 V AC 50/60 Hz according to IEC 60947-2 100% at 690 V AC 50/60 Hz according to IEC 60947-2 100% at 400/415 V AC 50/60 Hz according to IEC 60947-2. Tripping unit rating 2.5...4 A. Tripping unit technology: Thermal-magnetic. Magnetic tripping current: 51 A. Benefits: Complete protection concentrated in a single product. Compact and easy to select, TeSys GV2 motor circuit breakers are only 45mm wide and are categorised according to their level of features and functions: control type, breaking capacity, motor protection, and accessories. Applications: Industry, infrastructure, buildings, etc. Motor control and protection, in accordance with IEC 947-2 and IEC 947-4-1 standards. Easy to integrate into any configuration thanks to screw fixing or snap-on mounting profiles.