Information about Differential RCD 4P 80A 300mA Class AC
This Acti9 iID is a reliable modular residual current circuit breaker (RCCB). It is a 4P circuit breaker with a rated current of 80 A, an earth leakage sensitivity of 300 mA, and an AC type protection class. This product protects against electric shocks through indirect contact and fire hazards. It performs the function of disconnecting electrical circuits in the event of an earth fault. Its unique Visitrip indicator reduces intervention time by displaying the faulty device with a mechanical indicator on the front. This product also features a VisiSafe window with a green strip on the switch, indicating the complete opening of the poles, which allows downstream maintenance. This product complies with the EN/IEC 61008-1 standard. The rated breaking and short-circuit capacity (Im/m) is 1500 A. The conditional rated short-circuit current (Inc/c) is 10 kA. It has an electrical endurance of up to 10,000 cycles and a mechanical endurance of up to 20,000 cycles. The operating voltage Ue is 380 VAC to 415 VAC. The rated insulation voltage Ui is 500 VAC. The rated impulse withstand voltage Uimp is 6 kV. The frequency is 50 Hz or 60 Hz. It can be mounted on a DIN rail. The width in 9 mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 91mm x (D) 73.5mm. The weight is 0.37kg. In accordance with the IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.