Information about ID-K Differential 4P 25A 30mA AC Class
This is a residual current circuit breaker (RCCB) Acti9 ID K. It is a 4P circuit breaker with a rated current In of 25 A, AC type protection class, and earth leakage sensitivity of 30mA. This product protects against electric shocks from direct or indirect contact and fire hazards. A test button is used to check that the residual current device is functioning correctly. Connection is made downstream using a biconnect comb busbar or upstream/downstream using tunnel terminals. This product complies with the IEC/EN 61008-1 standard. The rated breaking capacity (Im/? ?m) and short circuit capacity is 500 A. The conditional short circuit current (Inc/? ?c) is 4.5kA. The electrical endurance is up to 2000 cycles. The mechanical endurance is up to 5000 cycles. The operating voltage Ue is 380VAC to 415VAC. The rated insulation voltage Ui is 440 VAC. The rated impulse withstand voltage Uimp is 4 kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 81mm x (D) 68mm. It has an IP20 protection rating. It becomes IP40 once in a modular enclosure according to IEC/EN 60529. The operating temperature is from -5°C to 40°C. The storage temperature ranges from -30°C to 70°C.