Information about IDD Differential 4P 25A 30mA Class AC
This iID Acti9 is a modular and reliable residual current circuit breaker (RCCB). It is a 4P circuit breaker with a rated current In of 25 A, AC type protection class, and an earth leakage sensitivity of 30mA. This product protects against electric shocks from direct or indirect contact and fire hazards. It performs the function of disconnecting electrical circuits in case of earth fault. Its unique VisiTrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on the front. This product also features a VisiSafe window with a green strip in the aisle indicating full pole opening, allowing for downstream maintenance. This product complies with the EN/IEC 61008-1 standard. The rated breaking and short-circuit capacity (Im/? ?m) is 1500 A. The rated conditional short-circuit current (Inc/? ?c) is 10kA. The electrical endurance is up to 15000 cycles. The mechanical endurance is up to 20000 cycles. The operational voltage Ue is from 380VAC to 415VAC. The rated insulation voltage Ui is 500 VAC. The rated impulse withstand voltage Uimp is 6 kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 91mm x (D) 73.5mm. The weight is 0.37 kg. It has an IP20 protection rating. It becomes IP40 once in a modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.