Information about Motor Protector MS116-1.6 1.00-1.60A
Manual motor protectors are electromechanical protection devices for the main circuit. They are primarily used to manually start and stop motors and provide less protection than fuses against short circuits, overloads, and phase failures. Reduced fuse protection saves costs, space, and ensures a quick response to short circuits, as it shuts down the motor in milliseconds. Starter combinations are equipped with contactors. The equipment features manual control/short circuit and overload current protection, adjustable current setting for load protection, magnetic trip indication, disconnection function, temperature compensation, remote control via undervoltage release and shunt trip, and short circuit breaking capacity (Ics) up to 100 kA. The reference 1SAM250000R1006 specifically is a motor protection circuit breaker. Its features include: Overload release current setting: 1 - 1.6 A, Instantaneous short circuit release setting range: 20A, With thermal protection, Phase failure sensitivity, Release technique: Thermomagnetic, Rated operating voltage: 690V, Rated permanent current Iu: 1.6A, Rated operational power in AC-3, 400 V: 0.55kW, Main circuit connection type: Threaded connection, Actuator element design: Rotary button (control), Device construction: Complete device in housing, Number of poles: 3.