Information about Motor protector MS116-16 10-16A
Manual motor protectors are electromechanical protection devices for the main circuit. They are mainly used to start and stop motors manually and to provide less protection to fuses against short circuits, overloads, and phase failures. Reduced fuse protection saves costs, space, and ensures a quick response to short circuits, as it shuts down the motor in milliseconds. The starter combinations are equipped with contactors. The equipment features manual control / protection against short circuit currents and overloads, the current setting is adjustable for load protection, and it has a magnetic trip indication, disconnection function, temperature compensation, remote control via minimum voltage release, and short-circuit breaking capacity (Ics) up to 100 kA. The reference 1SAM250000R1011 specifically refers to a motor protection circuit breaker. Its characteristics are: Overload release current setting: 10 - 16 A, Instantaneous short circuit release adjustment range: 240A, With thermal protection, Sensitive to phase failure, Release technique: Thermomagnetic, Rated operating voltage: 690V, Permanent rated current Iu: 16A, Rated operational power in AC-3, 400 V: 7.5kW, Main circuit connection type: Screw connection, Actuator element execution: Rotary button (control), Device construction: Complete device in housing, Number of poles: 3.