The Haier GT R290 16 kW Three-Phase (ref. AW16NMXGHA) is the most powerful model in the GT range, designed for large-scale installations or commercial use that require high performance and operational stability. Featuring natural refrigerant R290 and DC Inverter Twin Rotary technology, it provides heating, cooling, and domestic hot water with supply temperatures up to 80 °C without auxiliary resistance. Its monobloc design integrates a hydraulic pump, heat exchanger, and expansion vessel, offering a compact, quiet, and efficient installation.
Key Features
- A+++ efficiency with SCOP 4.80 (35 °C) and 3.85 (55 °C).
- Extended operating range: heating from –25 °C and cooling up to 48 °C.
- Water temperature up to 80 °C without electric backup (> –15 °C outdoor).
- Intelligent 2-zone control with independent circuits.
- Climate curves and automatic mode for adaptive comfort.
- Integrated DHW and solar thermal management as standard.
- Automatic anti-freeze protection and Smart Grid compatibility.
Energy Performance
- Heating (A7/W35): 16.00 kW · 3.23 kW input · COP 4.95
- Heating (A7/W55): 15.50 kW · 5.08 kW input · COP 3.05
- SCOP 35 °C: 4.80 (A+++) · ηs 189 %
- SCOP 55 °C: 3.85 (A+++) · ηs 151 %
- Cooling (A35/W18): 15.50 kW · 3.88 kW input · EER 4.00
- Cooling (A35/W7): 14.00 kW · 4.52 kW input · EER 3.10
Operating Ranges and Temperatures
- Outdoor: –25 ~ 35 °C (heating) / 10 ~ 48 °C (cooling) / –25 ~ 43 °C (DHW)
- Supply water: 20 ~ 80 °C (heating) / 5 ~ 25 °C (cooling)
- DHW tank: 25 ~ 75 °C
Design, Hydraulics, and Noise Level
- Compressor: 1 × High-reliability DC Inverter Twin Rotary.
- Hydraulic connections: R 1” inlet/outlet.
- Expansion vessel: 8 liters integrated.
- Noise level: 55 dB(A) pressure / 66 dB power.
Refrigerant
- Type: R290 (natural propane, low environmental impact).
- Charge: 1.25 kg · CO₂eq: 3.75 t.
Electrical Data
- Power supply: 380–415 V / 3 / 50 Hz (three-phase).
- Maximum current: 11.6 A · Recommended circuit breaker: 16 A.
Dimensions and Weight
- Dimensions (H × W × D): 880 × 1380 × 460 mm.
- Net/gross weight: 151 / 189 kg.
Included Accessories
- HW-WA101DBT wired controller (standard).
- ATW-A03N PCB box (built-in).
- Y-Type filter (standard).
Indicative Sizing
The 16 kW three-phase output is suitable for large buildings or high thermal consumption. As a reference, it can cover approximately:
- Well-insulated buildings (30–40 W/m²): 400–530 m²
- Medium insulation (50–60 W/m²): 265–320 m²
- Poor insulation (80–100 W/m²): 160–200 m²
Indicative values; always confirm by calculating thermal loads according to climate, emitters, and insulation level.