Information about VIGI NG125 A 4P 125A Differential Block I/S/R
This Vigi NG125 is an additional modular residual current device. It features 4 poles and a rated current of 125A. The earth leakage protection class is type A with a sensitivity of 300mA and voltage-independent technology. This product protects against short circuits, cable overloads, electric shocks from indirect contact, and fire hazards. This device is combined with an NG125 circuit breaker to provide earth leakage and circuit protection. The product complies with IEC 60947-2 standard. The rated operational voltage Ue ranges from 230 VAC to 415 VAC. The rated insulation voltage Ui is 690 VAC. The rated impulse withstand voltage Uimp is 8 kV. Pollution degree is 3. It can be mounted on a 35 mm symmetrical DIN rail. The width in 9mm modules is 11. Dimensions are (W) 207mm x (H) 118mm x (D) 81mm. Weight is 0.21 kg. The degree of protection is IP20 and IP40 in an enclosure.