Information about S&P Heat Recovery Unit CADB-HE-D12 ECOWATT left-horizontal
Heat recovery units CADB-HE-D 12 ECOWATT, featuring a high-efficiency counterflow plate exchanger (up to 93%), certified by EUROVENT, housed in white plastified galvanised steel casings, double-walled with non-flammable thermo-acoustic insulation (M0) made of 25 mm thick fibreglass in false ceiling versions (Models 04 to 21) and 50 mm in roof installation versions (Models 40 and 54). Configurable inlet and outlet ports, versions for horizontal installation and nozzles with a tight seal. Applications: Commercial premises, offices, hospitality, public buildings, schools. CADB/T-HE D ECOWATT: Heat recovery units without additional heating supply. CADB/T-HE DC ECOWATT: Heat recovery units with an integrated hot water coil. CADB/T-HE DI ECOWATT: Heat recovery units with integrated electric heating element. A 3-way control valve is supplied as an accessory. Motors: Models 04 to 21: EC motors with integrated electronic protection. IP44, class B. Models 40 and 54: Three-phase motors, Class F, IP55. Fans: Plug-fans with backward-curved blades. The fans incorporated in the CADB/T-HE ECOWATT models comply with the ErP Directive. Filters: F7: Low-loss F7 filters for air supply. M5: M5 filters for air extraction. Other data: Single-phase models (CADB-HE) and three-phase models (CADT-HE). Airflow rates from 400 to 5,400 m3/h at 150 Pa of available static pressure. All models and versions include an internal bypass. Interchangeable side panels allow for multiple combinations. CADB/T-HE 40 and 54 sizes with integrated frequency converter inside the unit (one converter per fan, allowing independent adjustment of supply and extraction airflow).