The Haier GT R290 10 kW Three-Phase (ref. AW10NMUGHA) is a high-performance monobloc air-to-water heat pump designed to meet the thermal comfort needs of large residential projects and small commercial installations. Its three-phase 380–415 V configuration ensures stable power supply and more efficient operation for high-demand applications. Featuring natural refrigerant R290, it can reach up to 80 °C water temperature without auxiliary heating, maintaining maximum A+++ efficiency even in extreme conditions down to –25 °C.
Key Features
- Energy efficiency A+++ with SCOP 5.10 (35 °C) and 3.83 (55 °C).
- Wide operating range: heating down to –25 °C and cooling up to 48 °C.
- Hot water up to 80 °C without electric backup when outdoor temp > –15 °C.
- Dual-zone control for independent climate management.
- Climate curves and automatic heating/cooling adjustment mode.
- Integrated DHW and solar thermal management.
- Automatic anti-freeze function and Smart Grid compatibility.
Energy Performance
- Heating (A7/W35): 10.00 kW · 1.96 kW input · COP 5.10
- Heating (A7/W55): 10.00 kW · 3.13 kW input · COP 3.20
- SCOP 35 °C: 5.10 (A+++) · ηs 201 %
- SCOP 55 °C: 3.83 (A+++) · ηs 150 %
- Cooling (A35/W18): 9.50 kW · 2.21 kW input · EER 4.30
- Cooling (A35/W7): 8.50 kW · 2.62 kW input · EER 3.25
Operating Ranges and Temperatures
- Outdoor: –25 ~ 35 °C (heating) / 10 ~ 48 °C (cooling) / –25 ~ 43 °C (DHW)
- Water supply: 20 ~ 80 °C (heating) / 5 ~ 25 °C (cooling)
- DHW tank: 25 ~ 75 °C
Design, Hydraulics, and Acoustics
- Compressor: 1 × DC Inverter Twin Rotary
- Hydraulic connections: R 1” inlet/outlet
- Expansion vessel: 4.5 liters integrated
- Sound level: 49 dB(A) pressure / 60 dB power
Refrigerant
- Type: R290 (natural propane)
- Charge: 0.9 kg · CO₂eq 2.7 t
Electrical Data
- Power supply: 380–415 V / 3 / 50 Hz
- Maximum current: 6.2 A · Recommended circuit breaker: 16 A
Dimensions and Weight
- Dimensions (H × W × D): 790 × 1250 × 380 mm
- Net/gross weight: 121 / 154 kg
Included Accessories
- HW-WA101DBT wired controller (standard)
- ATW-A03N PCB box (integrated)
- Y-Type filter (standard)
Indicative Sizing
Selection should be based on the building’s thermal load. As a guideline, 10 kW three-phase can cover approximately:
- Well-insulated buildings (30–40 W/m²): 250–330 m²
- Medium insulation (50–60 W/m²): 165–200 m²
- Poor insulation (80–100 W/m²): 100–125 m²
Indicative values; always confirm with a thermal load calculation according to climate and type of emitters.