Information about Differential ICV40N 1P+N C 16A 300mA Class AC
This Acti9 iCV40 is a residual current circuit breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 16 A rated current, and C curve tripping. The earth leakage protection class is type AC with a sensitivity of 300 mA. The time delay for earth leakage protection is instantaneous. The short-circuit breaking capacity with IEC rating is up to 6000A according to standard EN/IEC 61009-2-1. This product protects against short circuits, cable overloads, electric shocks from indirect contact, and fire hazards. Its 2 exclusive VisiTrip indicators reduce intervention time, as they show the faulty circuit and quickly identify the type of fault. Its green VisiSafe band ensures the physical opening of the contacts to allow downstream maintenance. This product complies with standard EN/IEC 61009-2-1. It has an electrical endurance of up to 20000 cycles and a mechanical endurance of up to 20000 cycles. The operating voltage Ue is 230VAC. The nominal insulation voltage Ui is 400 VAC. The nominal impulse withstand voltage Uimp is 4 kV. The frequency is 50/60 Hz. It is mountable on a DIN rail. The width in 9mm modules is 4. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 210g. According to standard IEC 60529, the degree of protection is IP20 and IP40 in the enclosure. The operating temperature is -5°C to 60°C. The storage temperature is -40°C to 85°C.