Information about Differential ICV40N 1P+N C 16A 300mA Class ASI
This Acti9 iCV40 is a residual current circuit breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 16 A rated current, and C curve tripping. The earth leakage protection class is type A-SI with a sensitivity of 300 mA. The time delay for earth leakage protection is instantaneous. The short-circuit interruption capacity with IEC rating is up to 6000A according to the EN/IEC 61009-2-1 standard. This product protects against short circuits, cable overloads, electric shocks from indirect contact, and fire hazards. Its 2 exclusive VisiTrip indicators reduce intervention time, as they show the faulty circuit and quickly identify the type of failure. Its green VisiSafe band ensures the physical opening of the contacts to allow downstream maintenance. This product complies with the EN/IEC 61009-2-1 standard. It has an electrical endurance of up to 20000 cycles and a mechanical endurance of up to 20000 cycles. The operational voltage Ue is 230VAC. The nominal insulation voltage Ui is 400 VAC. The nominal impulse withstand voltage Uimp is 4 kV. The frequency is 50/60 Hz. It is mountable on a DIN rail. The width is 4 modules of 9mm. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 210g. It has an IP20 protection rating. It becomes IP40 once integrated into a modular cabinet according to the IEC/EN 60529 standard. The operating temperature is from -25°C to 60°C. The storage temperature ranges from -40°C to 85°C.