Information about Differential IID 4P 40A 30mA
This iID Acti9 is a modular and reliable residual current device (RCCB). It is a 4-pole circuit breaker with a rated current of 40 A, a sensitivity of 30 mA, and a type A protection class. This product protects against electric shocks from direct or indirect contact and fire hazards. It performs the function of disconnecting electrical circuits in case of a ground fault. Its exclusive VisiTrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on the front. This product also features a VisiSafe window with a green strip in the aisle that indicates the complete opening of the poles, allowing for downstream maintenance. This product complies with the EN/IEC 61008-1 standard. The rated breaking and short-circuit capacity (Im/? ?m) is 1500 A. The conditional rated short-circuit current (Inc/? ?c) is 10kA. The mechanical endurance reaches 20,000 cycles, and the electrical endurance reaches 15,000 cycles. The operating voltage Ue is 380VAC to 415VAC. The rated insulation voltage Ui is 500 VAC. The rated impulse withstand voltage Uimp is 6 kV. The frequency is 50Hz or 60Hz. It is mountable on a DIN rail. The width of the 9mm steps is 8. The product color is white (RAL9003). The dimensions are (W) 72mm x (H) 91mm x (D) 73.5mm. The weight is 0.37 kg. It has an IP20 protection rating (according to IEC/EN 60529) and becomes IP40 once in a modular cabinet. The operating temperature is from -25°C to 60°C. The storage temperature ranges from -40°C to 85°C.