Information about ICV40N Differential 1P+N C 6A 30mA AC Class
This Acti9 iCV40 is a residual current circuit breaker with overcurrent protection (RCBO). It is a 1P+N automatic switch with 1 protected pole, a nominal input current of 6A, and a C tripping curve. The earth leakage protection class is type AC with a sensitivity of 30 mA. The earth leakage protection delay is instantaneous. The short-circuit breaking capacity with IEC rating is up to 6000A in accordance with standard EN/IEC 61009-2-1. This product protects against short circuits, cable overloads, electric shocks from indirect contact, and fire hazards. Its 2 exclusive VisiTrip indicators reduce intervention time by displaying the faulty circuit and quickly identifying the type of fault. Its green VisiSafe band ensures the physical opening of contacts to allow for downstream maintenance. This product complies with the EN/IEC 61009-2-1 standard. It has an electrical endurance of up to 20000 cycles and a mechanical endurance of up to 20000 cycles. The operational voltage Ue is 230VAC. The rated insulation voltage Ui is 400 VAC. The rated impulse withstand voltage Uimp is 4 kV. The frequency is 50/60 Hz. It is DIN rail mountable. The width is 4 modules of 9mm. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 210g. It has a protection degree of IP20 (according to IEC/EN 60529) and becomes IP40 once integrated into a modular cabinet. The operating temperature is -5°C to 60°C. The storage temperature is -40°C to 85°C.