Information about ID-K Differential 4P 63A 30mA AC Class
This Acti9 ID K product is a residual current circuit breaker (RCCB). It is a 4P breaker with a 63 A rated current, 30 mA earth leakage sensitivity, and AC type protection class. This product protects against electric shocks from direct or indirect contact and fire hazards. A test button is used to check that the residual current device is functioning correctly. Connection is made downstream using a biconnect comb busbar or upstream/downstream using tunnel terminals. This product complies with the IEC/EN 61008-1 standard. The rated breaking capacity (Im/? ?m) and short-circuit capacity are 500 A. The nominal conditional short-circuit current (Inc/? ?c) is 4.5kA. It has an electrical endurance of up to 2000 cycles and a mechanical endurance of up to 5000 cycles. The operational voltage Ue is 380VAC to 415VAC. The nominal insulation voltage Ui is 440 VAC. The rated impulse withstand voltage Uimp is 4 kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 81mm x (D) 68mm. According to the IEC 60529 standard, the degree of protection is IP20 and IP40 in the enclosure. The operating temperature is from -5°C to 40°C. The storage temperature ranges from -30°C to 70°C.