Information about Magnetothermal Circuit Breaker 24-32A
TeSys GV motor circuit breaker, 3 poles (3P), 32 A/690 V, for three-phase motor applications of 15 kW at 400 V. Provides thermal-magnetic protection with a thermal setting range of 24-32 A, magnetic tripping at 13 x In, and breaking capacity Icu of 10 kA at 400 V. Connection via screw terminals. Start/stop control by push-button guaranteed for 100,000 AC-3 cycles. Certified by various standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX), complies with Green Premium standard (RoHS/REACh).