Information about RCD IID 2P 25A 30mA Class AC
This product is a residual current circuit breaker (RCCB) Acti9 iID K. It is a 2P circuit breaker with a rated current of 25A, 30mA sensitivity with AC type protection class. This product protects against electric shocks from direct or indirect contact and fire hazards. There is a double clip for removal with a comb distribution bar in place. This Acti9 iID40 is dedicated to applications for small, medium and large buildings. This product complies with the EN/IEC 61008-1 standard. The rated breaking capacity (Im/? ?m) and short-circuit capacity is 500 A. The conditional rated short-circuit current (Inc/? ?c) is 4.5kA. The mechanical endurance reaches 5000 cycles and the electrical endurance reaches 2000 cycles. The operating voltage Ue is 220VAC to 240VAC. The rated insulation voltage Ui is 440 VAC. The rated impulse withstand voltage Uimp is 4 kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is white (RAL9003). The dimensions are (W) 36 mm x (H) 85 mm x (D) 69 mm. The weight is 0.21 kg. It has a degree of protection of IP20 (according to IEC/EN 60529) which becomes IP40 once in a modular enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.