Information about IC60N Magnetic Circuit Breaker 1P+N 40A Curve C
Magnetic thermal circuit breaker iC60N Acti 9, 1P+N, 40A, curve C, IP20, thermal-magnetic, suitable for disconnection, contact position indicator, lever control, tripping indicator, fixed mounting, DIN rail support, earth leakage protection with independent block, measures 85x36x78.5mm, weighs 0.25kg and is white. Breaking capacity: 10 kA Icu according to IEC 60947-2, 220...240 V AC 50/60 Hz, 36 kA Icu according to IEC 60947-2, 12...60 V AC 50/60 Hz, 36 kA Icu according to EN 60947-2, 12...60 V AC 50/60 Hz, 6000 A Icn according to EN 60898-1, 230 V AC 50/60 Hz, 20 kA Icu according to IEC 60947-2, 100...133 V AC 50/60 Hz, 10 kA Icu according to EN 60947-2, 220...240 V AC 50/60 Hz, 20 kA Icu according to EN 60947-2, 100...133 V AC 50/60 Hz, 6000 A Icn according to IEC 60898-1, 230 V AC 50/60 Hz, utilization category A according to EN 60947-2 and IEC 60947-2, suitable for disconnection according to IEC 60898-1, IEC 60947-2, EN 60898-1 and EN 60947-2, standards: EN 60947-2, IEC 60947-2, EN 60898-1 and IEC 60898-1.