Information about Motor Circuit Breaker GV2ME 6/10A
TeSys GV motor circuit breaker, 3 poles (3P), 10 A/690 V, for three-phase motor applications of 3-4 kW at 400 V. Provides thermal-magnetic protection with a thermal setting range of 6-10 A, magnetic tripping at 13 x In, and a breaking capacity Icu of 100 kA at 400 V. Connection via screw terminals. Start/stop control by push-button guaranteed for 100,000 AC-3 cycles. Certified by various standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX), meets the Green Premium standard (RoHS/REACh).